DTSF855/DSSF855 MODEL
THREE-PHASE ELECTRONIC MULTI-TARIFF ACTIVE ENERGY METER
Three-phase multi-tariff active energy meter
| Model No:DTSF855 (3phase 4wire)/DSSF855(3phase 3wire) |
Kinds: Electronic type multi-tariff kwh meter |
Basic current In(Imax): 1.5(6)A, 3(6)A, 5(20)A, 10(40)A, 15(60)A, 20(80)A, 30(100)A
|
Basic voltage : 3X220/380V or 3X57.7/100V(3phase 4wire);
3X100V; or 3X380V; (3phase 3wire)
3X220V (3phase 3wire, specail made) |
| Frequency:50Hz or 60Hz |
Accuracy:class 1 |
| Simple introduce: |
|
| it is used to measure three-phase four-wire (or three phase three wire )AC active energy consume, can store energy as per time and date. the energy measure unit is: kWh |
Detailed Product Description
Structure
- ADE7752 Measure Chip
- Palm machine programme,copy meter through infrared
- or RS485 communication port, together with computer to communicate
- Radio calibrate time function
- LCD displaying, LCD life>10years
- with pulse output terminals
- LED working index
- in the meter with programme switch
- in the meter (PCB board) with 1Hz time pulse output port
Technical data
- Standard: GB/T17215-2002; GB/T15284-2002;DL/T614-1997; DL/T645-1997
- Product Model: DTSF855 (3phase 4wire); DSSF855(3phase 3wire)
- Rated Frequency: 50Hz or 60Hz
- Accuracy: 0.5class or 1.0class or 2.0class
- Rated current::1.5(6)A, 5(20)A, 10(40)A, 15(60)A, 20(80)A,30(100)A (the others can be special made)
- Rated voltage:
3X220/380V or 3X57.7/100V(3phase 4wire);
3X100V; or 3X380V; (3phase 3wire)
3X220V (3phase 3wire, specail made)
- entironment conditions:
standard working temperature:-15°C~55°C
limited working temperature:-20°C~65°C
related humidity:<=85%
- Power loss:
Voltage circuit:≤2.0W 5VA; Current circuit:≤2.5VA
- Time clock Accuracy: <0.5S/d
- Starting Current: ≤0.4 In
- Fixed on Board: Vertical
- Multi-tariff Module: Four tariff, Eight time period
Function and Features
1. Measure Function
1.1 Can measure positive and reverse active energy consume.
1.2 Can judge following data if it is with correct working: Battery, Comunication, clock, energy directions etc.
1.3 The energy is seperately stored by differenct tariff
1.4 Reverse active energy consume measuring, except to measure it as positive direction, also record total time of reverse, total energy consume, and each time period of energy consume, and the last time reverse energy start and over time, and store data.
1.5 Can store 12months frozen data.
1.6 When power cut, all data will not lose, and store more than 10 years
1.7 Can initialization of total energy and each time period of energy.
2 Clock and time period, tariff function
3 Calibration time function
4 Displaying function
4.1 Can display 5 integral + 1 decimal
4.2 Displaying required data circulate, circulate period can be set from 2~30s,the default value is 10s
5 Communication function
6 Output function
7 Program function
8 Copy meter function
Size picture
Connection picture:

Packing
Packing Size |
Quantity |
Gross Weight |
43X31X29cm |
8pcs |
13KG |